Power transmission · Physics Class 11–12 | StemPy Lab
Course 21.3·Lesson 2 of 3
Power transmission
A line wastes the power I2r as heat. The current is I=P/V, so the loss is P2r/V2
about 35 min1 simulation3 practice questions1 Python program5 questions to check yourself
This lesson is free to read. Enroll free to keep your place and take the tests.
Lesson 2 of 3Show all lessonsHide
Try the code and the simulations beside the lesson.
Lighting a room that is far from the power station
The electricity that lights your room may have been made hundreds of kilometres away. It travels along wires. Wires have resistance, so they heat up. Every joule of heat in the line is a joule that never reaches your home. How do we send a lot of power over a long way and lose only a little?
The heat in the line
Let the power station send the power P at a voltage V. The line has a total resistance r, and the current in it is I. If the power factor is 1, the power sent is P=VI. We want I, so:
I=VP
The line has resistance, so it heats at the rate I2r. Put in the current:
Ploss=I2r=V2P2r
The share of the power that is lost is:
PPloss=V2Pr
The voltage V is squared in the bottom. If the voltage is ten times larger, the current is ten times smaller, and the loss is a hundred times smaller. This is why the voltage is raised for the journey.
Two rows that show the same power sent along the same line. In the top row a power station of 500 kilowatt is joined through a line of resistance 12 ohm directly to a town. The line current is 100 ampere and the heat in the line is 120 kilowatt, 24 per cent of the 500 kilowatt. In the bottom row a step-up transformer first raises the voltage from 5.0 kilovolt to 50 kilovolt, the same line carries only 10 ampere, and a step-down transformer at the town end lowers the voltage again. The heat in the line is only 1.2 kilowatt, 0.24 per cent of the 500 kilowatt.
A worked example
A power station sends 500 kW along a line of total resistance 12Ω. Compare the loss when it sends at 5.0 kV with the loss when it first steps the voltage up to 50 kV. The power factor is 1.
At 5.0 kV.I=VP=5.0×103V500×103W=100 A. The heat is I2r=(100A)2×12Ω=120000W=120 kW. This is 500120=24% of the power.
At 50 kV.I=50×103V500×103W=10 A. The heat is (10A)2×12Ω=1200W=1.2 kW. This is 5001.2=0.24% of the power.
The voltage went up ten times. The current went down ten times. The loss went down a hundred times, from 120 kW to 1.2 kW.
How much voltage is lost along the line? At 50 kV the current is 10 A. The voltage lost along the line is Ir=10A×12Ω=120 V. This is only 0.24% of 50000 V. At 5.0 kV the current is 100 A, and the voltage lost is 1200 V, which is 24% of 5000 V.
Take care: the voltage of the line is not across the line
A very common slip is to write the loss as rV2, with V the transmission voltage. Test it with the numbers above. At 50 kV it gives 12Ω(50000V)2=208 MW. This is far more than the 500 kW that was sent, which cannot be right.
The mistake is that V is the voltage between the two wires of the line, as measured at the station. It is not the voltage across the resistance of the line. Only the small voltage lost along the line, Ir, is across it. So the heat is I2r, or r(Ir)2, and never rV2.
From the power station to your socket
The electricity goes through several transformers on its way.
The alternator. The generator at the station makes an alternating voltage of about 11 kV.
The step-up transformer. It raises the voltage to a very high value for the long lines. In India the lines on tall towers carry 132, 220 or 400 kV.
The substation. A step-down transformer lowers the voltage to about 33 kV and then 11 kV for a town.
The pole transformer. Near your home a last step-down transformer gives the 230 V of the socket.
All of this works because the current is alternating. A transformer can raise or lower an alternating voltage with an efficiency of more than 95%. For a steady voltage there is no such simple device. Some very long lines now use direct current, with electronic converters at each end, but the loss I2r follows the same rule.
Why not thicker wire, or a still higher voltage?
We could also cut the loss by making r small, with thicker wires. But a thick copper or aluminium cable costs more and weighs more, and the towers would have to be stronger. A higher voltage costs too. The wires need larger insulators and must be kept farther from the tower and from the ground, and at the highest voltages the air starts to leak. Engineers choose a voltage and a wire so that the sum of all these costs is the least.
Power factor and the line
You have met the power factor of a circuit before. A load with a power factor cosϕ takes a current I=VcosϕP for the power P. A low power factor makes the current in the line larger, so the loss is larger by cos2ϕ1. A power factor of 0.8 makes the loss 1.56 times larger. So the supply companies ask big users to keep their power factor close to 1.
Start at 5 kV. Make the transmission voltage 10 kV. By what factor does the share lost fall? Now go back to 5 kV and set the power factor to 0.7. What happens to the loss?
Practise with new numbers
Try it in Python
The program sends 800 kW through a line of 10Ω at five different voltages. For each voltage it finds the current, the loss and the share lost.
Common mistakes
Writing the loss as V2/r. The voltage V is not across the line. Use I2r.
Forgetting that the current is P/V. Do not take the current as a fixed number. It changes when the transmission voltage changes.
Keeping kW or kV in a formula for W and V. Change them first: 1kW=1000W and 1kV=1000V.
Thinking that a higher voltage means a larger current. The same power at a higher voltage needs a smaller current.
Thinking the transformer makes power. It changes voltage and current. The power does not grow.
Mixing up the share lost and the loss. The loss is in watt. The share is the loss divided by the power sent.
Remember these
The line current is I=VP (power factor 1), or VcosϕP.
The heat in the line is I2r=V2P2r, and the share lost is V2Pr.
A transformer raises the voltage at the station and lowers it near the user. Ten times the voltage gives a hundred times less loss.
The voltage lost along the line is Ir. It is not the whole voltage of the line.
A low power factor raises the line current and the loss.
Check yourself
Try each one on your own first. If you are stuck, open a hint. Then check with Show the answer.
A power station sends 2.0 MW at 40 kV. What current is in the line?
Why is electric power sent at a very high voltage, and not at the 230 V that a house uses?
The voltage at which the power is sent is made three times larger. By what factor does the loss in the line change?
A line carries 20 A and has a resistance of 5.0Ω. What is the heat in the line, and what voltage is lost along it?